TDV Technical Data

ModelTDV 01 ATDV 02 ATDV 03 ATDV 04 ATDV 05 ATDV 06 A
Cooler versionDryDryDryDryDryDry
Cooling capacity (1) [kW]64127221304368461
Nominal water flow (1) [m3/h]6.012.020.828.634.042.6
Water pressure drop [bar]0.20.20.20.40.21.3
Total air flow [m3/h]24,78048,33075,340100,830126,330149,110
Dimensions [mm]L(3)[5] [mm]2150 (1975)3056 (2881)4206 (4031)5690 (5432)6850 (6582)8076 (7750)
L(4)[5] [mm] 2445 (2270)3595 (3420)4715 (4431)5940 (5756)7090 (6906)8254 (8064)
W [mm]1715
H [mm]2133
ModelTDV 01 ADTDV 02 ADTDV 03 ADTDV 04 ADTDV 05 ADTDV 06 AD
Cooler versionAdiabaticAdiabaticAdiabaticAdiabaticAdiabaticAdiabatic
Cooling capacity (1) [kW]112221365494611737
Nominal water flow (1) [m3/h]11.021.034.046.357.063.5
Water pressure drop [bar]0.60.50.51.00.52.7
Total air flow [m3/h]22,00044,00066,00088,000110,000132,000
Dimensions [mm]L(3)[5] [mm]2150 (1975)3056 (2881)4206 (4031)5690 (5432)6850 (6582)8076 (7750)
L(4)[5] [mm] 2445 (2270)3595 (3420)4715 (4431)5940 (5756)7090 (6906)8254 (8064)
W [mm]2115
H [mm]2133
Total installed power (2) [kW]2.304.306.308.3010.3012.30
Maximum absorbed current (2) [A]4.208.4012.6016.8021.0025.20
Axial Fans Qty./Diam. [No./mm]1/9002/9003/9004/9005/9006/900
Water content [l]6494209258316359
Hydraulic connection – in/out3″4
Fan controlPhase cut or VSD
ControllerElektronikonTM MK5S + SMARTLINK
Power supply [V/Ph/Hz)400/3+PE/50
Auxiliary voltage 24Vdc
Electrical approvalIEC/cULus
Pressure vessel approvalPED 2014/68/UE
(1) Reference condition: Ambient Air 35°C with RH=40%; Water in 50°C / out 40°C with/without pump; % Glycol=25%; Elevation above sea level=0
(2) Value specified for machine with “no pump”
(3) Overall dimensions without manifold
(4) Overall dimensions with manifold
(5) Value between brackets are referred to phase cut version variants